Studi Penentuan Kapasitas Pemutus Tenaga Sisi 20 kV Pada Gardu Induk 60 MVA Wonogiri

, Ahmadi and , Agus Supardi, S.T., M.T (2018) Studi Penentuan Kapasitas Pemutus Tenaga Sisi 20 kV Pada Gardu Induk 60 MVA Wonogiri. Skripsi thesis, Universitas Muhammadiyah Surakarta.

[img] PDF (Surat Pernyataan)
wedus.pdf

Download (346kB)
[img] PDF (Naskah Publikasi)
NASKAH PUBLIKASI PERPUS.pdf

Download (1MB)

Abstract

Abstrak Pada jaringan distribusi 20 kV sangat memerlukan sistem pengaman untuk perlindungan jaringan dan peralatan tenaga listrik terutama pada peralatan yang memiliki harga mahal seperti transformator tenaga. Sistem pengaman tenaga listrik minimum terdiri dari transformator ukur, relay, dan PMT atau CB (circuit breaker). PMT atau CB (circuit breaker) adalah alat untuk membuka dan menutup suatu rangkaian listrik dalam kondisi berbeban, serta mampu menutup dan membuka saat terjadi gangguan akibat hubung singkat. Tujuan penelitian ini adalah untuk mengetahui berapa besar kapasitas PMT atau CB (circuit breaker) yang dipakai pada Gardu Induk Wonogiri sesuai dengan ratingnya. Penentuan besar kapasitas PMT atau CB (circuit breaker) menggunakan metode perhitungan arus hubung singkat 3 fasa dimana memiliki arus hubung singkat yang paling tinggi. Ada 2 bagian hubung singkat 3 fasa yang harus dihitung yaitu arus hubung singkat bus 20 kV, arus hubung singkat penyulang. Setelah itu akan disimulasikan dengan menggunakan Etap 12.6 sebagai perbandingan dalam perhitungan besar arus hubung singkat yang terjadi pada jaringan distribusi. Dari hasil perhitungan matematis didapatkan nilai arus PMT atau CB (circuit breaker) sebesar 19.34 kA pada busbar 20 kV dan 14.22 kA pada penyulang sedangkan pada simulasi etap 12.6 didapatkan 19.32 kA pada busbar 20 kV dan 14.22 kA pada penyulang, sehingga memiliki perbedaan antara perhitungan matematis dan simulasi etap 12.6 pada busbar 20 kV yaitu sebesar 0.02 kA, maka kapasitas PMT atau CB (circuit breaker) pada busbar 20 kV dengan In 2000 A dan kapasitas 20 kA, pada penyulang dengan In 2000 A dan kapasitas 16 kA. Kata Kunci: Arus Hubung Singkat, PMT, Etap 12.6 Abstract in a 20 kV distribution network it is desperate for a safety system for the protection of networks and power equipment especially on expensive equipment such as power transformers. Minimum electrical power system consists of a transformer measuring, relay, and PMT or CB (circuit breaker). PMT or CB (circuit breaker) is a tool to open and close an electrical circuit in load condition, and able to close and open when interference caused by short circuit. The purpose of this study is to find out how much capacity of PMT or CB (circuit breaker) used on Wonogiri Substation in accordance with its rating. Determination of PMT or CB (circuit breaker) capacity using 3 phase short circuit current calculation method which has the highest short circuit current. There are 2 parts of short circuit 3 phase which must be calculated that short circuit bus current is 20 kV, short circuit short circuit. After that it will be simulated using Etap 12.6 as a comparison in the calculation of the large short-circuit current that occurs on the distribution network. From the mathematical calculation we get the value of PMT or CB (circuit breaker) flow of 19.34 kA on the busbar 20 kV and 14.22 kA in the repeater whereas in etet simulation 12.6 obtained 19.32 kA on busbar 20 kV and 14.22 kA at repeater, so as to have the difference between mathematical calculation and etap simulation 12.6 on busbar 20 kV that is 0.02 kA, the capacity of PMT or CB (circuit breaker) on busbar 20 kV with In 2000 A and capacity of 20 kA, in repeater with In 2000 A and capacity of 16 kA. Keywords: Short Circuit Flow, PMT, Etap 12.6

Item Type: Karya ilmiah (Skripsi)
Uncontrolled Keywords: Kata Kunci: Arus Hubung Singkat, PMT, Etap 12.6
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering
Divisions: Fakultas Teknik > Teknik Elektro
Depositing User: AHMADI
Date Deposited: 04 Aug 2018 06:14
Last Modified: 04 Aug 2018 06:15
URI: http://eprints.ums.ac.id/id/eprint/65068