Analisa Pengujian Bushing Pada Transformator Tenaga di Gardu Induk Wonogiri 150 kV

Maulana, Muhammad Jundu and , Jatmiko, S.T.M.T. (2018) Analisa Pengujian Bushing Pada Transformator Tenaga di Gardu Induk Wonogiri 150 kV. Skripsi thesis, Universitas Muhammadiyah Surakarta.

[img] PDF (Surat Pernyataan)
images.pdf
Restricted to Repository staff only

Download (594kB) | Request a copy
[img] PDF (Naskah Publikasi)
Revisi Naskah Publikasi Muhammad Jundu Maulana D400140081 2-2.pdf

Download (658kB)

Abstract

Abstrak Transformator adalah alat untuk menyalurkan tegangan tinggi ke tegangan rendah atau sebaliknya. Pada transformator terdapat komponen bushing yang berfungsi untuk menghubungkan kumparan transformator dengan rangkaian luar jaringan dan mendistribusikan tegangan ke konsumen. Perawatan dan pengujian pada bushing sangat perlu di perhatikan agar bushing tersebut dapat terhindar dari kerusakan. Tujuan penelitian ini adalah membahas tentang analisa pengujian transformator di tenaga PT. PLN (Persero) Gardu Induk Wonogiri. Pada bushing terdapat pengujian yang bertujuan untuk memastikan apakah bushing tersebut masih dalam kondisi layak di gunakan atau mengalami kerusakan. Metode untuk pengujian bushing menggunakan metode tan delta bushing yang bertujuan untuk memastikan apakah bushing tersebut masih layak di gunakan atau mengalami kerusakan dan menghindari panas pada bushing. Jika hasil nilai tan delta pada bushing di bawah 0,5 % maka bushing tersebut masih dalam kondisi layak digunakan sedangkan jika nilai tan delta pada bushing melebihi 0,5 % maka perlu dilakukan pengecekan atau mengganti bushing tersebut. Penelitian pengujian bushing pada transformator kali ini menunjukan bahwa bushing dalam kondisi di bawah nilai 0,5 % sehingga bushing masih dalam kondisi baik. Kata Kunci: pengujian bushing, tan delta transformator, transformator. Abstract Transformer is a tool to deliver high voltage to low voltage or vice versa. In the transformer there is a bushing component that serves to connect the transformer coil with the circuit outside the network and distribute the voltage to the consumer. Treatment and testing on bushing is necessary to note so that the bushing can avoid damage. The purpose of this study is to discuss about the analysis of transformer testing at PT. PLN (Persero) Substation Wonogiri. In bushing there is a test that aims to ascertain whether the bushing is still in a condition worthy of use or damage. Method for testing of bushing using tan delta bushing method that aims to ascertain whether the bushing is still feasible in use or suffered damage and avoid heat in the bushing. If the result of tan delta value on bushing is below 0.5% then the bushing is still in reasonable condition whereas if the value of tan delta at bushing exceeds 0.5% it is necessary to check or replace the bushing. Bushing testing research on transformer this time shows that the bushing in condition below the value of 0.5% so that the bushing is still in good condition. Keywords: testing bushing, tan delta transformer, transformer.

Item Type: Karya ilmiah (Skripsi)
Uncontrolled Keywords: Kata Kunci: pengujian bushing, tan delta transformator, transformator.
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering
Divisions: Fakultas Teknik > Teknik Elektro
Depositing User: MUHAMMAD JUNDU MAULANA
Date Deposited: 24 Jul 2018 12:21
Last Modified: 24 Jul 2018 12:29
URI: http://eprints.ums.ac.id/id/eprint/64086