Pamungkas, Unggul Adi and , Marwan Effendy, ST, MT, Ph.D (2017) Analisa Karakteristik Temperatur dan Kecepatan Udara Pada Ruangan Untuk kenyamanan Termal dengan Variasi Kecepatan Udara Menggunakan Metode Computational Fluid Dynamic (CFD) Disusun. Skripsi thesis, Universitas Muhammadiyah Surakarta.
PDF (Naskah Publikasi)
NASKAH PUBLIKASI.pdf Download (1MB) |
|
PDF (Halaman Depan)
Halaman Depan.pdf Download (1MB) |
|
PDF (Bab I)
BAB I.pdf Download (165kB) |
|
PDF (Bab II)
BAB II.pdf Restricted to Repository staff only Download (351kB) | Request a copy |
|
PDF (Bab III)
BAB III.pdf Restricted to Repository staff only Download (2MB) | Request a copy |
|
PDF (Bab IV)
BAB IV.pdf Restricted to Repository staff only Download (681kB) | Request a copy |
|
PDF (Bab V)
BAB V.pdf Restricted to Repository staff only Download (161kB) | Request a copy |
|
PDF (Daftar Pustaka)
DAFTAR PUSTAKA.pdf Download (257kB) |
|
PDF (Lampiran)
Lampiran.pdf Restricted to Repository staff only Download (214kB) | Request a copy |
|
PDF (Pernyataan Publikasi Ilmiah)
Surat Pernyataan Publikasi Ilmiah.pdf Restricted to Repository staff only Download (491kB) | Request a copy |
Abstract
This study aims to predict, as well as analyze the pattern of temperature distribution and air velocity in a room that has the installation of two split AC units. CFD simulation approach is applied in this study by preceded experimental measurements on actual conditions for data validation. In this study, the room measuring 10.45 m x 8.1 m x 3.92 m located in Room H 404 Faculty of Engineering serve as a simulation object. Three variations of air velocity measured at the front of the evaporator, ie at AC 1 unit 2,467 m / s, 3,733 m / s and 5 m / s, while AC unit 2 1,833 m / s, 2,733 m / s and 3,2 m / s becomes a parameter that is altered to investigate its effect on the distribution of temperature and air velocity. The simulation process begins with validating three different types of mesh 149328 element, 327440 element, 971209 element as the standard step that must be passed on simulation / computation based research to determine mesh construction that can produce simulation data than measurement data. The assumption in the simulation is empty space and there is no influence of heat from outside the room. (explain IC, BC, etc.) Based on the validation done, the mesh construction 971209 element is able to provide the most accurate prediction with the difference level with the measurement result of 4.53%. The simulation of three variations of air velocity across the evaporator shows that it does not have a significant effect on the average temperature in the room where the results are 23.73 ° C, 23.28 ° C and 23.77 ° C. While the average air velocity in the room there is an increase in each variation obtained results of 0.05 m / s, 0.08 m / s and 0.11 m / s.
Item Type: | Karya ilmiah (Skripsi) |
---|---|
Uncontrolled Keywords: | Computational Fluid Dynamic, Kenyamanan termal |
Subjects: | T Technology > TJ Mechanical engineering and machinery |
Divisions: | Fakultas Teknik > Teknik Mesin |
Depositing User: | UNGGUL ADI PAMUNGKAS |
Date Deposited: | 30 Oct 2017 07:13 |
Last Modified: | 30 Oct 2017 07:13 |
URI: | http://eprints.ums.ac.id/id/eprint/56591 |
Actions (login required)
View Item |